Easynet Brick Lane 1 Brick Lane, London, E1 6PU
Total Area 13,500 Square feet on 3 floors
Rack Space
1200mm X 800mm x 47U
Floor Loading
15kN
Carriers Easynet, BT, Virgin, COLT, Vodafone
Connectivity Available: LAN 100mb per customer to WAN. There after connectivity
is limited only be customer requirements (10Gbit circuits are
available)
Internal Cabling CAT6 and Fibre options
Mechanical Infrastructure
Environment Control Parameters Set Point 22degC +/- 2deg and Humidity 50% +/- 15% rh with
sensor tolerance
Air Conditioning System Liquid cooled air chilling / conditioning system
Computer Room Cooling Units (CRAC) N+1 DCCACUs
Features Roof mounted chiller plant comprises of 5 air-cooled liquid
chillers with each chiller operating at 80% of its capacity.
Should one chiller fail the BMS/ controls strategy system will
enable the operating chillers to maintain the total load of
the machine rooms by increasing operation on the
remaining 4 chillers to 100% capacity.
Water leak detection systems are installed in all machine
rooms and incorporate alarm panels linked to the building